INTRODUCTION TO NBT-2A SERIES
|
| |
FEATURES

Three phase EMI filter
In/output employ the terminal block
Both common mode and normal mode suppression form 50KHz to 30MHz
Good reliability and high performance
|
| |
APPLICATION
Numerical control machines
Industrial equipment like UPS, inverters and converters
Suitable for the FA equipment
|
| |
SHAPE AND DIMENSIONS
|
SHAPE AND DIMENSIONS
|
| MODEL |
NBT-2A040S |
NBT-2A050S |
NBT-2A060S |
NBT-2A080S |
NBT-2A100S |
| A |
272 |
272 |
272 |
364 |
364 |
| B |
292 |
292 |
292 |
394 |
394 |
| C |
312 |
312 |
312 |
424 |
424 |
| D |
120 |
120 |
120 |
145 |
145 |
| E |
90 |
90 |
90 |
115 |
115 |
| F |
90 |
90 |
90 |
120 |
120 |
| G |
6.5 |
6.5 |
6.5 |
6.5 |
6.5 |
|
SPECIFICATIONS

| MODEL |
NBT-2A040S |
NBT-2A050S |
NBT-2A060S |
NBT-2A080S |
NBT-2A100S |
| Rated Voltage AC(V) |
450 |
450 |
450 |
450 |
450 |
| Rated Current AC(A) |
40 |
50 |
60 |
80 |
100 |
Tested Voltage AC(V) One Minute, Line to Earth |
2000 |
2000 |
2000 |
2000 |
2000 |
Insulation Resistance (MΩ) 500V DC One Minute, Line to Earth |
≥500 |
≥500 |
≥500 |
≥500 |
≥500 |
Leakage Current (mA) 250V-60Hz |
≤3.5 |
≤3.5 |
≤3.5 |
≤3.5 |
≤3.5 |
| Voltage Drop(V) |
≤1.0 |
≤1.0 |
≤1.0 |
≤1.0 |
≤1.0 |
| Temperature Rise(deg.) |
≤30 |
≤30 |
≤30 |
≤30 |
≤30 |
Operating Temperature Range(℃) |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
NOTE
: Operating Temperature Range - Including temperature Rise