INTRODUCTION TO NFZ-5000 SERIES
|
| |
FEATURES

Three phase, four wire EMI filter
Ground choke included
Effective for both balanced and unbalanced three phase loads
Good shield effect by using metal case
|
| |
APPLICATION
Three phase DELTA systems
UPS power
Frequency inverters for speed motor regulations
|
| |
SHAPE AND DIMENSIONS
|
SHAPE AND DIMENSIONS

(mm)
| MODEL |
NFZ-5020GN |
NFZ-5030GN |
NFZ-5040GN |
NFZ-5050GN |
NFZ-5060GN |
NFZ-5080GN |
NFZ-5100GN |
| A |
328 |
328 |
328 |
328 |
328 |
390 |
410 |
| B |
145 |
145 |
145 |
145 |
145 |
145 |
145 |
| C |
65 |
65 |
65 |
120 |
120 |
120 |
120 |
| D |
280 |
280 |
280 |
280 |
280 |
280 |
280 |
| E |
240 |
240 |
240 |
240 |
240 |
240 |
240 |
| F |
205 |
205 |
205 |
205 |
205 |
205 |
205 |
| G |
175 |
175 |
175 |
175 |
175 |
175 |
175 |
| H |
M6 |
M6 |
M6 |
M6 |
M6 |
M8 |
M10 |
SPECIFICATIONS

| MODEL |
NFZ-5020GN |
NFZ-5030GN |
NFZ-5040GN |
NFZ-5050GN |
NFZ-5060GN |
NFZ-5080GN |
NFZ-5100GN |
Rated Voltage AC(V) |
450 |
450 |
450 |
450 |
450 |
450 |
450 |
Rated Current AC(A) |
20 |
30 |
40 |
50 |
60 |
80 |
100 |
Tested Voltage AC(V) One Minute, Line to Earth |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
2000 |
Insulation Resistance (MΩ) 500V DC One Minute, Line to Earth |
≥500 |
≥500 |
≥500 |
≥500 |
≥500 |
≥500 |
≥500 |
Leakage Current (mA) 250V-60Hz |
≤3.5 |
≤3.5 |
≤3.5 |
≤3.5 |
≤3.5 |
≤3.5 |
≤3.5 |
| Voltage Drop(V) |
≤1.0 |
≤1.0 |
≤1.0 |
≤1.0 |
≤1.0 |
≤1.0 |
≤1.0 |
Temperature Rise(deg.) |
≤40 |
≤40 |
≤40 |
≤40 |
≤40 |
≤40 |
≤40 |
Operating Temperature Range(℃) |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
-25 ~+85 |
NOTE
: Operating Temperature Range - Including temperature Rise
ATTENUATION CHARACTERISTIC
|
CIRCUIT DIAGRAMS
|
|